EB1140STZa
EVHA71/600100/EB1.140.S.TZ-a
TIAN-GUANGHVDCTRANSMISSIONPROJECTContractNo.:
CDEC-P97001H
IndexofRevisions
Rev.
Date
RevisedItems
Page
Remarks
0
30.09.2000
---
---
newissue
a
05.04.2002
changeswhilecommissioning;corrections
---
aftercommissioning
DC-Filters
Text11
Index:
1Introduction1-1
1.1GeneralInformation1-1
1.2DCFilters–GeneralDescription1-1
1.3DCFilterbankEquipment-Overview1-3
1.4Cubicles-Description1-6
1.4.1IGBTConverterCubicle+S11-6
1.4.2ElectronicSwitchCubicle+S21-7
1.4.3ControlandProtectionCubicle1-8
1.4.4ACDistributionCubicle+NE1(AuxiliaryPowerSupplyCubicle)1-9
1.4.5AirConditioning+UT11-9
2Controlandprotection2-1
2.1ProtectionofthePassivePart2-1
2.2Control+ProtectionoftheActivePart2-2
2.2.1ControlSystemoftheActivePart2-2
2.2.2ProtectionoftheActivePart2-4
3SafetyInstructions3-1
ListofTables:
Table1.21:
ListofDCfilterbanks1-2
ListofFigures:
Figure1.21:
DCfilterbanks-overview1-2
Figure1.31:
DCfilterpassivepartprimaryequipment(-Q3,–Q4onlyincaseofDCF3)1-3
Figure1.32:
DCfilteractivepartprimaryequipment1-4
Figure1.33:
ArrangementoftheequipmentintheDCfilterC+Pmodule1-5
Figure1.41:
MechanicalandelectricalarrangementintheIGBTconvertercubicle+S11-6
Figure1.42:
Mechanicalandelectricalarrangementintheelectronicswitchcubicle+S21-7
Figure1.43:
Mechanicalarrangementofthecontrolandprotectioncubicle+U11-8
Figure2.11:
DCfilterpassivepartprotectionscheme2-1
Figure2.21:
DCfilteractivepartcontrolscheme2-3
Figure2.22:
DCfilteractivepartprotectionscheme2-5
1Introduction
1.1GeneralInformation
Thison-sitetrainingmanualisashortintroductioninDCfilterequipmentanditscontrolandprotection.Everyitem,thatismentionedinthison-sitetrainingmanualisdescribedindetailintheoperationandmaintenancemanualslistedbelow.
∙EB3.7.1.6.TZ,OperationManual-LocalControlofActiveDCFilters
∙EB4.141.TZ,MaintenanceManual-DCFilterCapacitors
∙EB4.142.TZ,MaintenanceManual-DCFilterReactors
∙EB4.143.TZ,MaintenanceManual-DCFilterResistors
∙EB4.144.TZ,MaintenanceManual-DCFilterActivePart,incl.DCFilterProtection
∙EB4.510.TZ,MaintenanceManual-Arresters
∙EB4.645.TZ,MaintenanceManual-DCFilterCTs
Thison-sitetrainingmanualwillnotdealwithDCdisconnect-andgroundingswitches.Thissubjectisdescribedintheon-sitetrainingmanualbelongingtodisconnectandgroundingswitches.
Thison-sitetrainingmanualwillnotdealwithanymeasuringdeviceoutsidetheDCfilterdesignationlocation.Thissubjectisdescribedintheon-sitetrainingmanualbelongingtotheseitems.
1.2DCFilters–GeneralDescription
FortheTianGuangHVDCTransmissionProjectsixDCfilterbanksareprovided.Oneverysitethreefiltersarelocated.Twoofthethreefilterbanksarethestandardfilters,oneforeachpole.Thethirdfilterisredundant.Itcanberemoteswitchedtothedesiredpolebytheoperator.
AllthreeDCfilterbanksareequippedwithcomponentsofsameratings,soallthebankscanbeseenaselectricallysame.Eachfilterbankconsistsofadoubletunedpassivepartandaremovableactivepartthatistunedforsomeselectedharmonics.Tousethedcfilterwithorwithouttheactivepartithastobeconfiguredpriortoinsertion.
EachfilterbankisequippedwithitsownC+Pmodule.Thismoduleisalso,apartfromtheswitchingdevices,thehousingforthecomponentsoftheactivepart.
Table1.21liststheDCfilterbanksbylocationdesignations.
Tian
Guang
FilterBank
ActivePart
FilterBank
ActivePart
=11B03
=11GF03
=21B03
=21GF03
DCF1-Pole1
=12B04
=12GF04
=22B04
=22GF04
DCF2-Pole2
=10B05
=10GF05
=20B06
=20GF06
DCF3-Pole1orPole2
Table1.21:
ListofDCfilterbanks
Figure1.21showsthearrangementoftheDCfilterbanks.
Figure1.21:
DCfilterbanks-overview
1.3
DCFilterbankEquipment-Overview
TheDCfilterpassivepartprimaryequipmentconsistsofthecomponentslistedbelow:
∙capacitors–C1and–C2
∙reactors–L1and–L2
∙resistor–R1
∙arresters–F1and–F2
∙currenttransformers–T1,-T2and–T11
∙disconnectors–Q1,-Q2(and–Q3,–Q4incaseoftheredundantfilterbankDCF3)
∙groundingswitches-Q51and-Q52
Figure1.31givesanoverview.
Figure1.31:
DCfilterpassivepartprimaryequipment(-Q3,–Q4onlyincaseofDCF3)
TheDCfilteractivepartprimaryequipmentconsistsofthecomponentslistedbelow:
∙autotransformer-T101(MVroom)
∙IGBTconverter(IGBTconvertercubicle+S1)
∙voltagetransformer–T5(IGBTconvertercubicle+S1)
∙currenttransformer–T1(IGBTconvertercubicle+S1)
∙electronicswitch-S2(electronicswitchcubicle+S2)
∙IGBTconvertertransformer–T11(MVroom)
∙HFfiltercapacitor–C1(MVroom)
∙arrester–F1(MVroom)
∙bypassswitch–Q6(outdoorequipment)
∙disconnector–Q9(outdoorequipment)
∙groundingswitch–Q8(outdoorequipment)
Figure1.32givesanoverview.
Figure1.32:
DCfilteractivepartprimaryequipment
TheDCfilterC+Pmoduleisdividedintotwocompartmentswhichformthecontrolroomincludingallcubicles,andthemediumvoltageroom.
Thecontrolroomcomprisesthecomponentslistedbelow:
∙auxiliarypowersupplycubicle+NE1
∙IGBTconvertercubicle+S1
∙electronicswitchcubicle+S2
∙C+Pcubicle+U1
∙aircondition+UT1
Themediumvoltageroomcomprisesthecomponentslistedbelow:
∙IGBTconvertertransformer–T11
∙HFfiltercapacitor–C1
∙arrester–F1
∙autotransformer–T101
Thewallbushings–Z1and–Z2connecttheindoorequipmentwiththeoutdoorsswitchingdevices.Figure1.33showsasketchoftheequipmentarrangement.
Figure1.33:
ArrangementoftheequipmentintheDCfilterC+Pmodule
1.4Cubicles-Description
ThissectiongivesanindividualdescriptionofthecubicleslocatedintheDCFilterModule.
1.4.1IGBTConverterCubicle+S1
TheIGBTconverterishousedinaStandard8MFSIEMENScubicle.Inadditionthecubiclehasarooftopwithfansforforcedcooling.The(main)componentsdescribedinthefollowingareinstalled:
∙semi-controlledthree-phasethyristor/diodebridge(3units–A41,-A43,-A45):
rectifierfor490 VACpowersupply
∙PCCmodule–A4:
pre-chargecontrolboardfortherectifier
∙DClinkcapacitor(10cans-C1…-C10):
stabilisestheDCvoltageproducedbytherectifier
∙voltagetransformer–T5:
measurestheDClinkvoltage
∙single-phaseinverter(4x2IGBT–V11,-V12,–V21,-V22,–V31,-V32,–V41,-V42):
producestheoutputvoltagefromtheDClinkvoltage
∙PICANSTmodule-A3:
IGBTfiringcircuitmodule
∙currenttransformer–T1:
measuresthecurrentthroughtheIGBTs
∙PICADAmodule–A100:
signalinterfacecircuitboard.
Figure1.41:
MechanicalandelectricalarrangementintheIGBTconvertercubicle+S1
TheIGBTConverterCubicleisfedfromtheAutotransformer–T101with500VAC.Thisvoltageisrectifiedandtheresulting2*500VAC700VDCisstabilisedintheDClinkcapacitor.ControlledbytheC+Pcubicle+U1theIGBTinverterproducesfromtheDClinkvoltagetheoutputvoltagerequiredtoreducetheharmonicsintheDCtransmissionline.
1.4.2ElectronicSwitchCubicle+S2
TheelectronicswitchishousedinhousedinaStandard8MFSIEMENScubicle.Itisrealisedwithamodified3phaseSITORthyristorassembly(Series6QG35)ofSIEMENSmanufacturing.Theoriginalsurgesuppressercircuitofeachthyristorpairhasbeenremovedandanewcircuit(commonforallthreethyristorpairs)hasbeenestablishedinthecubiclebelowtheSITORassembly.
Twothyristorpairsareusedfornormaloperation.Inadditionapassivethyristor-firingmoduleisinstalled.Thisisconnectedtothethirdthyristorpair.IncasemalfunctionofthecontroloftheSITORand/ortheIGBTconverteranovervoltageoftheDClinkoftheIGBTconvertercanoccur.AnovervoltagedetectioncircuitattheDClinktriggersthispassivethyristor-firingmodule.ItwillbypasstheIGBTconverterbyfiringthethirdthyristorpairbeforeanimpermissibleharmfulovervoltageisreached.
PleasenotethattheSITORassemblyhasbeenmodifiedandthereforenotallinformationwithintheoperationmanualisvalid.The(main)installedcomponentsarelistedbelow:
∙modified3phaseSITORthyristorassembly–S2
∙controlledthyristorfiringmodule–A10
∙passivethyristorfiringmodule–A20
∙fanunit–E1
∙mountingplate–A1forsurgesuppressingcomponents–C1,-C2,-C3,-R1,-R2
∙surgesuppressingcomponent–L1
Figure1.42:
Mechanicalandelectricalarrangementintheelectronicswitchcubicle+S2
TheelectronicswitchisconnectedtotheoutputvoltageterminalsoftheIGBTconvertercubicle+S1andtheLVsideoftheIGBTconvertertransformer–T11.DuringinsertandremovesequenceoftheactivepartandwhiletheactivepartisinsertedbuttheIGBTinverterisnotoperatingbecauseofanyreason,theelectronicswitchisfired.Sothecurrentinthelowvoltagesideoftheactivepartisflowingthroughtheelectronicswitch.ThisprotectstheIGBTinverterfromovercurrents.
1.4.3ControlandProtectionCubicle
TheDCfilterprotectionandtheactivepartcontrolarehousedinadoublesizeStandard8MFSIEMENScubicle.TheC+Pisrealisedwiththemulti-microprocessorsystemSIMADYND.Thesystemsareinstalledinseparatesidesofthedoublesizecubicleandareelectricallyandmechanicallydecoupledenablingrepairsinafaultysystemwithoutdisturbingthehealthysystem.
Figure1.43:
Mechanicalarrangementofthecontrolandprotectioncubicle+U1
-A1,-A2RacksofSimadyn D
+.C,+.HMeasuringcircuit