The Configuration and Communication of Integrated Substation Automation Systems 配置及变电站综合自动Word格式.docx
- 文档编号:1463880
- 上传时间:2023-04-30
- 格式:DOCX
- 页数:15
- 大小:26.69KB
The Configuration and Communication of Integrated Substation Automation Systems 配置及变电站综合自动Word格式.docx
《The Configuration and Communication of Integrated Substation Automation Systems 配置及变电站综合自动Word格式.docx》由会员分享,可在线阅读,更多相关《The Configuration and Communication of Integrated Substation Automation Systems 配置及变电站综合自动Word格式.docx(15页珍藏版)》请在冰点文库上搜索。
Basedonadiscussionofthefeatureofasubstation,thepaperpresentstheconceptthatasubstationiscomposedofbasicunits(BC).ThehardwarestructureoftheIEDofaBCisdescribed.Next,thepaperdiscussesthecommunicationmodeofthecurrentintegratedSubstationAutomationSystems(ISA)anddescribesthehardwarestructureandthefunctionsoftheISAwithfieldbus.AtlastthepaperpresentstrendsinthedevelopmentofISA.
Keywordssubstationautomationcommunicationfieldbus
1.Introduction
Sincethebeginningof90`s,hundredsofISAsystemhavebeenputintooperationinChina.Thesesystemshaveplayedaveryimportantroleinsubstationperformancehavebeendemonstratedinmanyways.Thissystemshouldbeamulti-functionintegratedanduniformlydesignedrealtimecontrolsystemwithhighefficiencyandreliability.Itshouldimplementamostallthefunctionsofsecondaryequipmentofmodernsubstation,realizetherealtimedatasharingandexchange,andshouldbeexpandableforfutureuse.HowtodesignanISAsystemtomeetalltheaboverequirementsisdiscussedinthepaper.
First,afteradiscussionofthefeatureofsubstation,thepaperpresentstheconceptthatasubstationiscomposedofbasicunits(BC),suchaslines,transformers,bussesandVoltAmpereReaction(VAR)compensationequipment,andsoon.ThecircuitbreakersandswitchesaremergedintherelevantBCsastheirattachedcontrolfacilities.ThehardwarestructureofaBCisdescribed.Next,thepaperdiscussesthecommunicationmodeofthecurrentISAandpointsoutthefieldbuswouldbethewaytorealizereliable,real-timeandaccurateinformationcommunicationamongintelligentelectronicdevice(IED).Then,ifpresentstheconfigurationandfunctionsofthedistributedISAwithfieldbus.Atlast,thepaperpresentstrendsinthedevelopmentofISA.
2.BasicUnitsandConstruction
Asubstationisaveryimportantunitinpowersystemforpowertransmissionanddistribution.Asubstationisrequiredtoruncontinuously,reliablyandstably.Substationsofvariousvoltagelevelsandcapacityhaveasimilarconfigurationwhichiscomposedofpowertransmissionanddistributionfacilitiessuchastransformers,VARdeviceswithdifferentvoltagelevels.Thedistinctionbetweendifferentsubstainsisthequantityandvoltageleveloffacilitiesandthewayconnectiononly.
Tomonitorandcontrolthesubstationoperation,abusisequippedwithpotentialtransformers(PT)andtherearecurrenttransformers(CT)ineachwindingofthetransformer,eachlineandtheswitchgearbayoftheVAPequipment.INthesecondarysystem,instantaneousvaluesofvoltageandcurrentareobtainedthroughPTandCT,andthesevaluesarefurtheranalyzedandprocessedtogiveoperationaldataofthesubstationsuchasvoltage,currentandpoweretc.Nom-electricaldatasuchasoiltemperatureandgassignalsarealsoprovidefortransformersandVARequipment.Statusdataofcircuitbreakers,isolatorswitchesandotherauxiliaryequipmentintheswitchgearbaysaregatheredthroughauxiliarycontactsandtransducers.Thesubstationsecondarysystemcollectsandprocessesallthesedatatodetectanyfaultorabnormality.Ifthereisafault,thesecondarysystemwillsendoutacircuitbreakertrippingcommandtotheswitchbaycorrespondingtothefaultedequipmentsothatthefaultcanbeisolated.Ifthereisabnormality,awarningsignalwillbegiven.
Ithasbeenshownbyrelevantreferencethatthefaultcharacteristicsofbuses,lines,transformersandVARequipmentaredifferentfromeachotherasaresultoftheirdifferentphysicalfeature.Thereforerequirementsfortheirmonitoringandcontrolaredifferentfromeachother.
Forfaultsinlines,transformers,VARequipmentorbuses,therearenoothercontrolmeasuresthantrippingthecircuitbreakersofthecorrespondingequipment.
Undernormaloperationcondition,transformersandVARequipmentparticipateinvoltageandVARcontrolcoordinatedbythesystemtomeettherequirementsofpowernetworkvoltagelevelandVARcompensation.
Coordinatedbythesecondarysystem,severalcircuitbreakersmaybecontrolledtomaintainpowersystemstabilityorpowersupplyreliabilityofthesubstation.Commonexamplesareunderfrequencyloadsheddingandbusautomatictransfer.
Tosummarize,themainfeaturesofasubstainsystemare:
Buses,lines,transformersandVARdevicesarethebasicequipmentinasubstation.Theyfunctiontogethertotransferanddistributepower.
Requirementsforthemonitoringandcontrolofbuses,lines,transformersandVARdevicesdifferfromeachother.
Alargeamountofdatainasubstationisfromswitchgearbays,asmalldatatothem.
Protectionandmeasurementformonitoringhavethesamedatasourcebutdifferentrequirementsforsamplingfrequencyandcontrolalgorithms.
Relayprotectionisafundamentalfunctionanditsnormaloperationshouldbeensuredevenifotherdevicesfailtowork.
Thereislittleinformationexchangebetweenswitchgearbays.
Thecontrolofacircuitbreakerinswitchgearbaysmayhavevariouscausesuchaslinefaults,lossofsystemsynchronism,equipmentoverloading,underfrequencyloadshedding,normalnetworkoperationsandsoon.Whateverthecauseis,theoperationisthecontrolofcircuitbreakers.
TransformersandVARdeviceshavetwokindsofcontrol,i.e.,controlinfaultcondictionsandinnormalsystemoperations.
Basedontheaboveanalysisandfromthepointofviewofmonitoringcontrolandmanagementofpowertransferanddistributioninsubstation,thispaperproposesthatasubstationconsistsofsuchBCsasbuses,lines,transformers,VARequipmentandsoon.ABCprovidesdatathroughoneorseveralswitchgearbaystoandreceivescontrolcommandsfromthesecondarysystem.EachBChasitsowncharacteristicsandrequirementsformonitoringandcontrol.
ThusaBCinsubstationcanbetreatedasabasicresearchobjectofmonitoringandcontrol.Thesetofallbasicresearchobjects,managed,coordinatedandcontrolledbythesubstationmaincomputer,formaanISAsystem.
ThehardwarestructureofaBCisnotedasIED.AccordingtothefunctionalrequirementsofaBC,IEDisdesignedbythefaultindependentruleandfunctionindependentrule.EachBChasitscorrespondingIEDwhichmainlydiffersinI/OinterfacesfromthatofanotherBC.Forexample,thetransformerIEDnotonlyinterfaceswithtemperatureandpressuretransducers,butalsohasalargernumberofI/OthanalineIEDhas,Itmustcontrolallthebreakersonthesideofeachwindingunderfaultconditionsandcontroltheon-loadtap-changerundernormaloperations.TheIEDofaVARdeviceoralineBCprovidesaserialporttocommunicatewithaintelligentVARdevice,ortheprotectiondevicelocatedontheothersideofaline.AtypicalIEDhardwarestructureofaBCisshowninFig,.1.
TheAC/DCsamplingandBinaryI/OpartsareconnectedtoabaythroughPT/CTandopticalinsulators,acquiringdatafromthebayandcontrollingthebreaker.TheProcessControlpartanalyzes,calculatesandprocessestheacquireddata,andperformsprotectionfunctionsbytrippingthebreakeriffaultsaredetected.ThroughFieldbusinterface,anIEDcommunicateswiththesubstationcomputersystem(SCS)orotherIED.IttransmitsrealtimedatatotheSCSforsupervisionandreceivescommandsfromSCSorotherIEDforcontrol.
MMIisusedfordisplayingtheacquireddataandparameters,testingandmaintenanceoftheIED.
ThebusIEDacquiresdirectlythecurrentandstatusdatafromthebaysanddetectsbusfaults.Ifafaultisdetected,allbreakersofallunitsconnectingthebusaretrippedbythebusIED.
ThefunctionofunderfrequencyloadsheddingisrealizedbythebusandlineIED,coordinatedbytheSCS.
3.InformationExchangeandFieldBus
ThecommunicationinterfacebetweenthecurrentIEDofISAismainlybyRS-422/485seriesportandonlyafewisbylocalareanetwork(LAN).UsingRS-422/485communicationinterface,thelinkamongnodescanbedone,butthenumberofnodeslinkedcannotbemorethan32andcannotsuitthefuturedemandsofISA.Inaddition,thecommunicationmodeismaster/slaveandhasdrawbackasfollows:
Onlyonenodeismaster,andtheothersareslavesinthecommunicationnet.Ifthemasternodeisatfault,thesystemwillimmediatelyfail.
Thecommunicationmodeofmaster/slavestructureisunbalanced.Theslaverespondstothecommandsfromthemasterandsendsdatatothemaster.Theefficiencyofdatatransmissionislowandimportantdataintheslavecannotbetransmittedimmediatelyuntilitreceivesthecommandfromthemaster.Thelargerthesystemscale,thelowerthereal-timeofsystemperformance.
Themaster/slavecommunicationmodecannotmeettherequirementsofcommunicationbetweenanytwonodes.
UsingRS-422/485seriesportinterface,itiseasytoconnecteachother.ButtheprotocolamongtheIEDisdifferentandnostandardinchinaisfollowed.Therefore,thecommunicationcontroliscomplicatedanditisdifficulttorealizehigh-speed,reliableandaccurateinformationexchangebetweenIED.Themediaforcommunicationislimitedandsystemsengineersareoccupiedwithprogrammingandtestingcommunicationsoftware.ApplyingLANtechnology,thedatacanbetransmittedinhighspeedandthefunctionsofcentralprocessing.Butinthefieldofprocesscontrol,theadvantagesofLANarelessobviousowingtothefollowingreasons:
·
IntheLAN,largequantityofdataaretransmittedinapackageofmessage,buttheyarenotfrequentlytransmitasmall
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- The Configuration and Communication of Integrated Substation Automation Systems 配置及变电站综合自动 配置 变电站 综合
链接地址:https://www.bingdoc.com/p-1463880.html