小点数Small Intelligent说明书.docx
- 文档编号:10665288
- 上传时间:2023-05-27
- 格式:DOCX
- 页数:29
- 大小:299.23KB
小点数Small Intelligent说明书.docx
《小点数Small Intelligent说明书.docx》由会员分享,可在线阅读,更多相关《小点数Small Intelligent说明书.docx(29页珍藏版)》请在冰点文库上搜索。
小点数SmallIntelligent说明书
CONTENTS
CHAPTER1OVERVIEW
2
CHAPTER2TECHNICALFEATURESOFLN1010CONTROLUNIT
3
CHAPTER3SYSTEMSTRUCTUREOFLN1010CONTROLUNIT
4
3.1IntelligentDetectingDevices
4
3.2ActiveEncodingDevices
4
3.3PassiveEncodingDevices
4
CHAPTER4LN1010CONTROLUNITFUNCTIONS
6
4.1ControlUnitInOperation
6
4.2ControlUnitInAlarm
6
CHAPTER5MANIPULATIONGUIDEFORLN1010CONTROLUNIT
11
5.1DirectManipulation
11
5.2ManipulationIn“KeyLockOff”Status
11
5.2.1SystemParameterSetup
12
5.2.2LoopDeviceRegistration
12
5.2.3AlarmRecord
14
5.2.4AutomaticControlRelation
16
5.2.5SystemTest
17
5.2.6Programming
18
CHAPTER6JBF-11S/CE2GASEXTINGUISHINGPANELMANIPULATION
21
CHAPTER7JBF-11S/CD6MULTI-LINEDIRECTCONTROLPANELMANIPULATION
25
CHAPTER1OVERVIEW
JB-QB/LN1010FireAlarmControlUnitisakindofdual-wirebussmallintelligentautomaticfirealarmdevice,designedformedium,smallfirecontrolprojects.Itcanbeusedtogetherwithdetectors,manualcallpoints,hydrantbuttons,inputmodulesandoutputmodulestoformautomaticfirealarmsystem.
JB-QB/LN1010FireAlarmControlUnitisalarmonlytype,withoutprintingfunction;
JB-QB/LN1010/PFireAlarmControlUnitisalarmonlytype,withprintingfunction;
JB-QB-JBF-11S/CE2GasExtinguishingControlUnitcouldmonitor2gasextinguishingzones,withprintingfunction;
JB-QB-JBF-11S/CD6ControlUnit(AutomaticControlType)has6multi-lineautomaticcontrolzones,withprintingfunction;
JB-QB/LN1010andJB-QB/LN1010/Phave2modelsavailableeach:
LN1010/127andLN1010/64.
LN1010systemadoptssoftaddressencodingtechnology.Communicationsbetweendetectorsandfirealarmcontrolunitsarethroughnonpolarity2-wirebus,thussimplifieswiringlayout,freelayoutpathandmethod,withoutprecedenceorder.Easytodesignandconstruct.Alsoreducesthewirelength,increasesreliabilityofwiringlayoutandlowerprojectcost.
LN1010systemconnectstointelligentdetectorsbyusingwavefilteringandvariablethresholdtechnologytoanalyzefeedbacksignalsfromdetectors,thusreducingfalsealarmratecausedbytransientinterference,increasingfirealarmreliability.
LN1010seriescontrolunitswithbuilt-inblackboxfunction,havefirealarminformationautomaticstorefunction,includingalarmtype,alarmtimeandlocaldeviceaddress.Userscouldlookupfirealarmhistoryeasily.
LN1010systemhaslargeLCDscreenwithEnglishorChinesemenu,foreasyoperation.
LN1010systemhaslocalautomaticcontrollogicprogrammingfunction,tomeetthepracticalautomaticcontrolrelationdesignofprojects.
LN1010systemcoulduseEnglishorChinesetoremarkalarmaddress.Userscouldchoosetoviewinformationbetweenremarkandaddressnumber.Easytoswitchbetweenboth.
LN1010ControlUnithasautomaticprintingfunction,couldachievereal-timefirealarmprintingfunctioneverytime.
LN1010FireAlarmSystemissuitableforcomputerroom,Disco,hotel,apartment,library,warehouse,bankandothersmall-scalefirealarmplaces.
CHAPTER2TECHNICALFEATURESOFLN1010CONTROLUNIT
LN1010seriescontrolunitsarecompatiblewith
SystemCapacity
Singleloop,maximum127alarmpoints,23automaticcontrolpoints;
Display
LCDdisplay,EnglishorChinesemenu;canremarkloopaddress;easytoswitchbetweenalarmaddressnumberandalarmaddressremarks;
WiringSystem
Detectors,manualcallpointsandinputmodulesareconnectedtoL1,L2terminalsoncontrolunitloopcardbynonpolarity2-wirebus;
AutomaticControlOutput
Canprogram23automaticcontrolpointslocally;
InspectionPeriod
≤3seconds;
DetectorPowerSupply
24VDC,pulse;
CommunicationDistance
≤1500m;
PowerSupply
Main:
AC220
50Hz;
Backup:
DC24V,2.5Ah;
OperatingTemperature
0℃~50℃;
RelativeHumidity
92±3%(40±2℃);
Weight
5kg;
Dimensions
Wall-mountingstyle;
500mm(height)×360mm(width)×100mm(thickness).
InstallationDiagram:
CHAPTER3SYSTEMSTRUCTUREOFLN1010CONTROLUNIT
Localcomponentsconnectedtocontrolunit:
3.1IntelligentDetectingDevices
3.1.1LN2100IntelligentPhotoelectricSmokeDetector
3.1.2LN2110IntelligentHeatDetector
3.2ActiveEncodingDevices
3.2.1
JBF-101FIntelligentmanualCallPoint:
Pressdowntotriggeralarm;connecttoL1,L22-wirebus;hasaseparategroupofpassivecontactitself.WhenJBF-101Fisusedashydrantbutton,oneactionfeedbackterminalisconnectedtofirepump.Feedbackindicatorisconnectedtoagrouppassivecontactinfirepumpcontrolcabinetbytwodirectlines;
3.2.2
JBF-131FIntelligentSignalInputModule:
Connectto2-wirebuslinesL1,L2tocontrolfirecontroldevices,suchaswaterindicator,pressureswitch,fixed-temperaturefireproofswitch,etc.connectagroupofpassivecontactonlocaldevicetoinputterminalsofJBF-131F,whetherdevicehasbeenactivatedornotcouldbemonitoredbyLN1010controlunitthroughL1,L22-wirebus;
3.2.3
JBF-171FBusIsolationModule:
whenusingonelooptomonitormultiplefloors,shouldinstallbusisolationmoduleateachfloorentrancetoavoidsystembreakdowncausedbyshortcircuit.EachJBF-171Fcouldconnect32localdevicesatthemost.
3.3PassiveEncodingDevices
3.3.1
JBF-141FBusAutomaticControlModule:
AutomaticcontroloutputmoduleonlyneedL1,L2bustoachievepassivecontactoutputfunction,suchasbroadcastingandelevatorcontrol.Need24VDCforlocaldevicescontrolledbyautomaticcontrolmodule.Needtwomorepowerlinestocutoffheavycurrentpowersupplyandactivate/stopofheavycurrentequipment;
3.3.2
JBF-152F/CGasExtinguishingModule:
Necessaryequipmenttocontrolgasrelease.Gasreleasewarningindicator,sounderbeacon,andtankopeningtoreleasegascanonlybecontrolledbyJBF-152F/C.EachmoduleneedsixwirestoconnectwithLN1010controlunit,whichareactivate,stop,actionfeedback,devicefeedback,24VDCpowersupplyandGND;
3.3.3
JBF-151FAutomaticControlRelayModule:
Connectedtodirectcontrolpaneltocontrolimportantfirecontroldevices,suchas:
firepump,sprinklerpumpandfans,etc;switchandisolatebetweenlowvoltagelinesofautomaticcontrolsystemandhighvoltagelinesofcontrolleddevices;preventhighvoltageentersintosystem,ensuresystemsafety;usedtoenhancecapacityofbuscontrolmodulecontactoutput;EachmoduleneedsixwirestoconnectwithLN1010controlunit,whichareactivate,feedbackandGND.
LN1010ControlUnitSystemDiagram:
LN1010ControlUnitLoopCardTerminalConnectionDiagram(AlarmonlytypeorGasextinguishingtype):
CHAPTER4LN1010CONTROLUNITFUNCTIONS
4.1ControlUnitInOperation
Whenswitchedon,controlpanelneeds10secondstoinitialize,“Initialization”isshownonscreen.SeeFigure4-1below.
Figure4-1SystemInitialization
Inoperation,controlunitdisplaysthecontrolconditionsofcurrenttime,powersupplystatus,keyboardstatusandautomaticon/offstatus.Inspectionindicatorblinking,mainandbackuppowersupplyislit,evergreen,shownasinFigure4-2.
Figure4-2SystemInOperation
4.2ControlUnitInAlarm
Controlunitautomaticallyinspectspartalarm,faultinspection,autocontrolon/off,busdevicecheckandpowersupplyoperationstatuscheckcontinuouslytoensuresystemrunningnormally.Controlunithas3alarmsounds:
firealarmsoundduringfirealarmandautomaticcontroloutput(firetrucksound),faultsoundwhenreportingfault(ambulancesound)andautomaticcontrolfeedbacksound(shortandrapidsound).
4.2.1BusDeviceFault
Ø“Fault”indicatoroncontrolpanelison,withfaultalarmasmadebyambulance,press“Silence”toeliminatesound;
ØClockrunningnormally,screenshowstotalfaultalarmnumber,faultalarmaddressandalarmtime.Iffirstfaulthappenson09:
18,faultalarmaddressis023,totalfaultalarmnumberis001,asFigure4-3.Iftherearemorethanonefaultalarms,press“↕”toviewotherfaultalarminformation.Aftereliminatingallfaults,alarmsoundgoesoff,faultalarmdisplaydisappears,screendisplayreturnstonormal;
ØPrintercouldprintoutalarmtype,faultaddress,normaladdressinformation,dateandtime.
Figure4-32DisplayStatusofFaultAlarm
Controlunitreportsbusdevicefaultalarmmaycausedbyfollowingreasons:
ØDetectorbroken,needtobereplaced;
ØDetectorwasencodedwrongaddress;
ØLooseconnectionbetweendetectorbaseandbus;
ØLoosecontactbetweendetectoranddetectorbase;
ØIfreportalldetectorfaults,mightbecontrolunitfault,checkvoltagefallsonL1andL2bymultimeter,normally,around20V.
4.2.2BusShortCircuitFault
IfthereexitsshortcircuitbetweenL1andL2,controlunitreportloopfault,asinFigure4-4.
Figure4-4BusShortCircuitFault
Tobussystem,anypartofshortcircuitwillbereportedasloopfault;ifbuswithisolator,controlunitwillnotreportloopfault,butreportfaultonalllocalcomponentaddressesbehindbusisolator.Aftercircuitisrecovered,isolatorisresetautomatically,thewholesystemreturnstonormal.
BusShortCircuitFaultmaybecausedbyfollowingconditions:
ØInnormalcondition,controlunitrunningwithfullloads,resistancebetweentwobuslinesshouldbearound7kΩ;
ØBusshortcircuitcausedbyinstallation;
ØDetectorbroken,likewaterwentintodetectors;
ØControlunitfault.Todistinguishiffaultiscausedbyloop,localcomponentsorcontrolunititself,itisonlyneedtodisconnectbusfromcontrolunit.Iffaultstillexists,itiscontrolunitfault;
ØToconnectnewlocalcomponents,powersupp