1、武汉市体育馆中央空调毕业设计范本模板摘要 本设计是武汉市某体育馆的舒适性中央空调的设计,建筑共分三层,此建筑用途有主会场、办公室、会议室、训练馆等。大会场及训练馆采用集中式的送风方式,对于周边的的办公室,会议室等小房间则采用风机盘管加独立新风的送风方式,对于三楼的几个小房间则采用家用空调分体机。空调冷源由两台螺杆式冷水机组提供,热源由锅炉经过板换后提供。冷冻水系统采用闭式水平同程式,垂直异程式。关键词:集中式,风机盘管加独立新风,分体机。AbstractThe design is a Stadium in Wuhan City, the comfort of central air-condi
2、tioning design, the building is divided into three layers, the building uses the main venue, offices, conference rooms, training hall。 Field of the General Assembly and training center with centralized air around the office, conference room and small room fan coil independent fresh air supply air, h
3、ome air conditioners for the third floor of a small room body aircraft。 Air conditioning cooling source is two screw chillers, heat from the boiler after the change of the board. The chilled water system using the closed level of the same program, the vertical different programs。Keywords: centralize
4、d, fan coil units, plus independent fresh air, split type。第一章 工程概况1。1 工程概况:本设计对象为武汉市某体育馆,场馆主要有:办公室,会议室,训练馆,播音、积分、声控、以及主厅等.场馆主要分为三层,其中只有训练馆有地下层。工程位于武汉市,东经11413,北纬31.总空调面积为10090。42m2。本工程空调设计的任务包括本场馆的中央空调系统的设计及通风设计。本中央空调系统设计要求能够实现夏季供冷,并能满足人体的舒适性要求。1.2 武汉市室外空调设计参数:台站位置:北纬31, 东经11413。气象参数为:夏季:大气压:100.17
5、kpa 室外日平均温度:31.9 室外相对湿度:79%室外干球温度:35。2 室外湿球温度:28。2 室外平均风速:2.6m/s冬季:大气压:102。33 kpa 采暖计算温度:-2 空调计算温度:-5 相对湿度:76 室外平均风速:4.2m/s1。3室内空调主要设计参数表2.1 室内设计参数 房间名称温 度(波动范围2)相对湿度(波动范围10)新风量m3/(h人)夏季冬季夏季冬季小办公室2618604030值班室2618604030大办公室2618604030大训练用房2618604050小训练用房2618604050外管理室2618604025控制室2618604025电视转播室26186
6、04030会议室2618604040售票室2618604025内管理室2618604025贵宾室2618604050接待室2618604050运动员休息2618604030更衣室2618604020医务室2618604050裁判用房2618604030新闻发布2618604030尿检室2618604050记者用房2618604025冷饮吧台2618604020播音室2618604030灯控、声控室2618604030计时、计分室2618604030体育馆主厅2618604020第二章 负荷计算表2.1 围护结构参数序号围护名称类型传热系数(w/。)传热衰减传热延迟(h)夏季冬季01外墙砖墙15
7、240-40。900.910.1712。4402外窗单框双玻璃窗2。712.781。000。3803内墙砖墙0010011.761.760.408。4904内门木框夹板门2.172.170.990。8405楼板楼面-261。071.070.1511.5706屋面现浇08-2-7020。920。930。407。962.1冷负荷计算本建筑的冷负荷采用逐时温差计算法。2。1。1外墙和屋面瞬变传热引起的冷负荷Qc()=AK(tc()+td)kktR 式中 Qc() 外墙和屋面瞬变传热引起的逐时冷负荷,W; A - 外墙和屋面的面积,m2; K 外墙和屋面的传热系数,W/(m2 ),由暖通空调附录22和
8、附录23查取; tR 室内计算温度,; tc() 外墙和屋面冷负荷计算温度的逐时值,,由暖通空调附录24和附录25查取; td - 地点修正值,由暖通空调附录2-6查取; k 吸收系数修正值,取k=1.0; k 外表面换热系数修正值,取k=0。9;2.1。2内围护结构冷负荷 Qc()=AiKi(to。m+ttR) 式中 ki 内围护结构传热系数,W/(m2 ); Ai 内围护结构的面积,m2;to。m 夏季空调室外计算日平均温度,;t 附加温升,可按暖通空调表2-10查取。2。1。3外玻璃窗瞬变传热引起的冷负荷Qc() = cw Kw Aw ( tc() + td - tR) 式中 Qc()
9、外玻璃窗瞬变传热引起的冷负荷,W; Kw 外玻璃窗传热系数,W/(m2 ),由暖通空调附录2-7和附录2-8查得; Aw 窗口面积,m2; tc() 外玻璃窗的冷负荷温度的逐时值,由暖通空调附录2-10查得; cw 玻璃窗传热系数的修正值;由暖通空调附录2-9查得; td 地点修正值,由暖通空调附录211查得;2.1.4透过玻璃窗的日射得热引起的冷负荷Qc() = C Aw Cs Ci Djmax CLQ 式中 C 有效面积系数,由暖通空调附录215查得;Aw 窗口面积,m2;Cs 窗玻璃的遮阳系数,由暖通空调附录2-13查得;Ci- 窗内遮阳设施的遮阳系数,由暖通空调附录2-14查得;Djm
10、ax 日射得热因数,由暖通空调附录212查得;CLQ 窗玻璃冷负荷系数,无因次,由暖通空调附录2-16至附录219查得;2.1.5照明散热形成的冷负荷白炽灯 Qc() = 1000 N CLQ 日光灯 Qc() = 1000 n1 n2 N CLQ 式中 N 照明灯具所需功率,W; n1镇流器消耗功率稀疏,明装时,n1=1。2,暗装时,n1=1.0; n2灯罩隔热系数,灯罩有通风孔时,n2=0。50。6;无通风孔时,n2=0.60。8; CLQ-照明散热冷负荷系数,由暖通空调附录2-22查得。2。1.6人体散热形成的冷负荷1、人体显热散热形成的冷负荷Qc() = qs n CLQ 式中 qs
11、- 不同室温和劳动性质成年男子显热散热量,W,由暖通空调表2-13查得; n 室内全部人数; 群集系数,由暖通空调表2-12查得;CLQ 人体显热散热冷负荷系数,由暖通空调附录2-23查得;2、人体潜热散热引起的冷负荷 Qc() = ql n 式中 ql 不同室温和劳动性质成年男子潜热散热量,W,由暖通空调表2-13查得;n,同式3-61。2。2人体散湿负荷人体散湿量可按下式计算 D = 0.001n g式中 D 散湿量,/ h ; 群集系数,由暖通空调表2-12查得为0。80; n 计算时刻空调房间内的总人数; g - 一名成年男子的小时散湿量,由暖通空调表213查得。下面选择1001办公室
12、进行计算,本设计的负荷将用软件算出。房间负荷源逐时负荷值8910111213141516171819201001办公室房间参数面积38。88m2高度5。75m室内温度26.0相对湿度60人体5人照明300W设备2000W新风150.00m3/h西北内墙基本信息长5.5高(宽)5。75面积5.5*5.75传热系数1.86负荷值347。1347。1347.1347。1347.1347.1347.1347。1347。1347。1347。1347.1347。1西南外窗基本信息长20。7高(宽)2面积7.2*5。75传热系数2.6负荷值638.2894.1111212632022369959937654
13、684242251754629。7557东南内墙基本信息长5。5高(宽)5.75面积5。5*5。75传热系数1。86负荷值347。1347。1347。1347。1347。1347。1347。1347.1347。1347。1347.1347.1347。1东北内门基本信息长1高(宽)2面积21传热系数3。5负荷值41.341.341.341.341。341.341。341。341.341。341。341。341.3楼板基本信息长5高(宽)1.08面积5。47。2传热系数0。59负荷值135。3135。3135。3135。3135.3135.3135.3135.3135.3135.3135.3135
14、.3135。3新风显热426。3426.3426。3426.3426.3426。3426.3426.3426。3426。3426。3426。3426。3全热1501149114621415135512861214114210761020977.7951。3942。3湿负荷1。491。481.431。371。281。191。090.990。890.810。750。720.71人体显热278。3278。3278。3278。3278.3278。3278.3278。3278.3278。3278.3278。3278.3全热615.5615。5615。5615。5615.5615。5615。5615.56
15、15.5615.5615.5615.5615。5湿负荷0.50.50.50.50。50.50。50。50.50。50.50.50。5照明负荷值210210210210210210210210210210210210210东北内墙基本信息长6.85高(宽)5。75面积7.25.752传热系数1。86负荷值432.4432.4432。4432.4432.4432。4432。4432.4432。4432。4432。4432.4432.4设备负荷值1501501501501501501501501501501501501501001办公室小计冷负荷(W)291731733390354243005978
16、8272993391206504403329082836新风冷负荷(W)1501149114621415135512861214114210761020977.7951.3942。3总冷负荷(W)441846644852495756567264948611075101967524501138603778湿负荷(kg/h)0.50。50。50.50。50.50.50.50.50。50.50.50。5新风湿负荷(kg/h)1。491.481.431。371。281。191.090。990.890.810.750.720。71总湿负荷(kg/h)1.991.981.941.871.791。691。5
17、91.491。391。321.261。221。21冷指标(W/m2)7581.687。291.1110.6153.8212.8255。5234.6167.3103.774.872.9新风冷指标(W/m2)38。638.337。636。434。933.131。229。427.726.225。124.524。2总冷指标(W/m2)113.6120124.8127。5145.5186。8244284.9262。3193。5128。999。397.2总湿指标(kg/hm2)0。050。050。050.050.050。040。040。040.040.030。030.030。03每个房间的最大时刻的负荷楼
18、号楼层房间工程负荷最大值时刻的各项负荷值冷负荷新风冷负荷新风湿负荷总湿负荷新风冷指标总冷指标总湿指标新风量WWkg/hkg/hW/m2W/m2kg/hm2m3/h1号楼1层1001办公室9933.11141。90。991.4929.4284。90。041501002办公室9933。11141.90。991.4929。4284.90.041501003办公室5086。3228。40.20。311。7273。40.02301004值班室4962。4228。40。20。2611。72670。01301005办公室9933。11141。90.991.4929。4284.90。041501006办公室9
19、933。11141.90.991。4929.4284。90。041501007训练用房4740.72040。31。633。9139.8132.20.083001008管理10489500。40.50。6212.9282.70.02501009控制室29963500.40。50。628。6522.40。01501010值班室5356.4250。20。250。3112.9288。40。02251011电视转播室5703.9600。40.60.7230.9324.30。04601012会议室(25人)18073100079。9312.44171。6481.50.2110001013售票室136943
20、58。70.30.59。2361.40.01501014内部管理室2552.9500。40。50.77.344。60.01501015内部管理室1673250。20.250.357.356.20.01251016贵宾室22052001.41。992.3949。1103.10.062001017接待室2246。12001.41.992.3947.11000。062001018贵宾室22052001.41.992.3949.1103。10.062001019内部管理室1673250.20。250。357.356。20。01251020内部管理室2552.9500。40.50.77。344.60.0
21、1501021训练用房2144。22001.41。992。3937。176.80.042001022训练用房2144.22001.41.992.3937.176。80。042001023运动员休息2791。33002.22.983.9887.8169.40。123001024更衣室2275。32001。41.992.991032200。152001025医务室1650。61000.70.991.1933.989。80。041001026裁判用房2263.5900。70.891。1923。281.40。03901027新闻发布5910。67505。47.459.95109.7196.10.157
22、501028尿检1653。21000。70。991.233.989.90.041001029记者用房4332。95003.64。966.99128.7240。10。185001030运动员休息2791.33002.22.983.9887。8169.40.123001031更衣室2275。32001.41.992。991032200.152001032大训练馆77529100189.9317.5211.7102。40.0210002层2001管理大2047500.40.50.714.573.70.02502002管理大2047500.40.50.714.573.70。02502003管理大204
23、7500。40。50。714.573.70.02502004管理1226250.20。250。3517。2101。20.02252005管理1226250.20。250.3517。2101。20。02252006管理大2047500.40.50。714。573。70。02502007管理大2047500.40。50。714。573。70.02502008管理大2047500.40.50.714。573.70。02502009冷饮吧台19374456.70。390。6911.7510.10。02603层3001播音室4148.11200.91.191。5922100.10.031203002灯控,声控室5674.21801。31.792.3923.296.10.031803003计时,计分室4148.11200。91.191。5922100。10.031203004体育馆大空间1128326.31004742。6994.131500。95118。9252.40.18101080工程合计2687855.2799458674。31211。21684。48003。72.28108795第三章 空调系统方案确定3.1 空调水系统方案表31 冷水系统优缺点类型特征优点缺点闭式管路系统不与大气相接触,仅在系统最高点设置膨胀水箱与设